| 产品规格型号 Specification |
| 产品规格型号 Model | PAU unit | |||
| 安装方式 Type | PAU-A2600S | |||
| 性能 Performance | 温度控制范围 Temperature control range | 20 to 30 | ||
| 温度控制精度 Temperature control accuracy | ?.2 | |||
| 制冷功率 Cooling capacity(W) | 2100/2450 | |||
| 允许环境温度 Allowable ambient temperature | 20 to 35 | |||
| 允许环境湿度 Allowable ambient humidity(RH%) | 10 to 85(No condensation) | |||
| 外观 Appearance | 体积 Outside dimensions(mm) | H1065×W450×D700(except flange) | ||
| 重量 Weight(kg) | 100 | |||
| Blower duct joint diameter(mm) | ?50 | |||
| Coating color | Unit | Ivory(JPMA Y22-85B semi-gloss) | ||
| Controller | Dark gray(JPMA Y55-40B semi-gloss) | |||
| 电源 Electrical characteristics |
电源 Power supply |
3 phase AC200V 50/60Hz | ||
| 电流 Operating current(A) | 17/17 | |||
| Operating power(kW) | 5.5/5.5 | |||
| 组成装置Components | Compressor, Coolant | Rolling piston rotating type, HFC-134a | ||
| Condenser, Cooler | Fin and tube | |||
| Heater |
Sheathed heater with fin (4.5kW?) | |||
| Blower air discharge rate (m3/min) |
Blower fan for condenser | 16.0/18.8 | ||
| Coolant controller | Capillary tube | |||
| Temperature sensor | IC Temperature sensor | |||
| 温度控制 Temperature control | Electronic digital setting indicating PID control | |||
| 保护装置Protective device |
Main circuit | Ground leakage breaker(30A 30mA) Reverse-phase protection relay | ||
| Blower fan (For cooler) |
Overcurrent relay Delay timer (For 3 minutes) Surge-absorbing unit | |||
| 压缩机 Compressor | Low temperature operation prevention thermostat Overcurrent relay Motor protector Surge-absorbing unit | |||
| Heater | Overheat protection thermostat Thermal fuse(99篊 OFF) | |||
| Alarm device |
Alarm lamp | Lamp illuminates | ||
| Note: Temperature setting range: These values are obtained at the air discharge port of the PAU unit in a surrounding environment of 25篊/40% RH. The PAU unit may not offer the rated temperature control accuracy depending on the ambient temperature/humidity. Blower air discharge rate: Make sure that you do not excessively reduce the volume of the evolving airflow to prevent freezing. (For more information, please contact our sales representative.) Cooling capacity: These values are obtained in a surrounding environment of 25篊/40% RH. Allowable ambient temperature: Performance does not cover all temperature control ranges. *The protection circuit for operation in low temperature operates in ambient temperatures of 18篊 or lower. (The unit recovers to its normal state at 20篊 or higher.). |