您现在的位置  首页 >> 代理贸易业务 >> Apiste PAU精密空调 >> PAU精密空调 >> [ PAU-S2900EX ]

产品名称:PAU-S2900EX
产品型号:PAU-S2900EX
上传时间:2012-06-01
点击次数:12756

   

 产品规格型号  Specification
产品规格型号 Model PAU unit
安装方式 Type PAU-S2900EX
性能 Performance 温度控制范围 Temperature setting range 20 to 30(When compressor is off: 20 to 40)
温度控制精度 Temperature control accuracy(g) 【0.5
湿度控制范围 Humidity setting range -
湿度控制精度 Humidity setting accuracy -
制冷功率 Cooling capacity(W) 2500/2900 (At ambient temperature of 25ìCì)
加湿能力 Humidification capacity -
允许环境温度 Allowable ambient temperature 10 to 35
允许环境湿度 Allowable ambient humidity(RH%) 10 to 85(No condensation)
外观 Appearance 重量 Weight(kg) 79(Except control box)
体积 Outside dimensions(mm) H500×W750×D600
(except flange, drain pipe, etc.)
Blower duct joint diameter(mm) ┆150
Coating color Unit: Ivory(JPMA: Y22-85B semi-gloss)
Controller: Dark gray(JPMA: Y55-40B semi-gloss)
电源 Electrical
characteristics
电源 Power supply 3 phase AC 100V 50/60Hz
电流 Operating current 22.0 (At ambient temperature of 25ìCì)
电机功率 Power consumption 4400 (At ambient temperature of 25ìCì)
组成装置 Components 压缩机 Compressor Rolling piston rotating type
Coolant, Coolant volume(g) R-134a  420
Condenser, Cooler Fin and tube
Heater Sheathed heater with fin (3200W)
除湿器 Humidifier -
Blower air discharge rate 0.8/1.0
(*at connection duct 0.4/0.7 or higher)
30/34
Coolant controller Capillary tube
Temperature sensor Thermocouple(Type K)
Humidity sensor -
温度控制 Temperature controller Electronic digital setting indicating PID control
除湿控制 Humidity controller -

 

Note:
Temperature setting range:
These values are obtained at the air discharge port of the PAU unit in a surrounding environment of 25ìC/40% RH. The PAU unit may not offer the rated temperature control accuracy depending on the ambient temperature/humidity.

Blower air discharge rate:
This unit is not provided with a blower fan motor. When using this unit, be sure to connect the FFU. When the airflow in the FFU is insufficient, the EMERGENCY lamp illuminates.
Make sure that you do not excessively reduce the volume of the evolving airflow to prevent freezing. (For more information, please contact our sales representative.)

Cooling capacity:
These values are obtained in a surrounding environment of 25ìC/40% RH.

Allowable ambient temperature:
Performance does not cover all temperature control ranges.

Performance:
Performance is obtained at the air discharge port when this unit is connected to PAU-A 17FFU with a ┆150 duct.

*The protection circuit for operation in low temperature operates in ambient temperatures of 18ìC or lower. (The unit recovers to its normal state at 20ìC or higher.).

[打印]  [关闭窗口]  

Warning: Unknown: Your script possibly relies on a session side-effect which existed until PHP 4.2.3. Please be advised that the session extension does not consider global variables as a source of data, unless register_globals is enabled. You can disable this functionality and this warning by setting session.bug_compat_42 or session.bug_compat_warn to off, respectively in Unknown on line 0