产品规格型号 Specification |
产品规格型号 Model | PAU unit | |
安装方式 Type | PAU-SU2900L | |
性能 Performance | 温度控制范围 Temperature setting range | 20 to 30(When compressor is off: 20 to 40) |
温度控制精度 Temperature control accuracy(g) | 【2.5 | |
湿度控制范围 Humidity setting range | - | |
湿度控制精度 Humidity setting accuracy | - | |
制冷功率 Cooling capacity(W) | 2400/2900 (At ambient temperature of 35ì) 2000/2200 (At ambient temperature of 25ìCì) | |
加湿能力 Humidification capacity | - | |
允许环境温度 Allowable ambient temperature | 10 to 35 | |
允许环境湿度 Allowable ambient humidity(RH%) | 10 to 85(No condensation) | |
外观 Appearance | 重量 Weight(kg) | 107 |
体积 Outside dimensions(mm) | H1250×W1200×D250(Except flange) | |
Blower duct joint diameter(mm) | ┆150 | |
Coating color | Unit: Ivory(JPMA: Y22-85B semi-gloss) Controller: Dark gray(JPMA: Y55-40B semi-gloss) | |
电源 Electrical characteristics |
电源 Power supply | 1 phase 100V 50/60Hz |
电流 Operating current | 20.0 (At ambient temperature of 25ìC) | |
电机功率 Power consumption | 4.2 (At ambient temperature of 25ìC) | |
组成装置 Components | 压缩机 Compressor | Rolling piston rotating type |
Coolant, Coolant volume(g) | HFC-134a 460 | |
Condenser, Cooler | Fin and tube | |
Heater | Sheathed heater with fin(3.0KW) | |
除湿器 Humidifier | - | |
Blower air discharge rate | 16.0 / 18.8 | |
Coolant controller | Capillary tube | |
Temperature sensor | Thermocouple(Type K) | |
Humidity sensor | Thermistor | |
温度控制 Temperature controller | Electronic digital setting indicating PID control | |
除湿控制 Humidity controller | - |
Note:
Temperature setting range:
These values are obtained at the air discharge port of the PAU unit in a surrounding environment of 25ìC/40% RH. The PAU unit may not offer the rated temperature control accuracy depending on the ambient temperature/humidity.
Blower air discharge rate:
This unit is not provided with a blower fan motor. When using this unit, be sure to connect the FFU. When the airflow in the FFU is insufficient, the EMERGENCY lamp illuminates.
Make sure that you do not excessively reduce the volume of the evolving airflow to prevent freezing. (For more information, please contact our sales representative.)
Cooling capacity:
These values are obtained in a surrounding environment of 25ìC/40% RH.
Allowable ambient temperature:
Performance does not cover all temperature control ranges.
Performance:
Performance is obtained at the air discharge port when this unit is connected to PAU-A 17FFU with a ┆150 duct.
*The protection circuit for operation in low temperature operates in ambient temperatures of 18ìC or lower. (The unit recovers to its normal state at 20ìC or higher.).