您现在的位置  首页 >> 代理贸易业务 >> Apiste PAU精密空调 >> PAU精密空调 >> [ PAU-A920S-HC ]

产品名称:PAU-A920S-HC
产品型号:PAU-A920S-HC
上传时间:2012-06-01
点击次数:8448

   

 产品规格型号  Specification
产品规格型号 Model PAU unit
安装方式 Type PAU-A920S-HC
性能 Performance 温度控制范围 Temperature setting range(篊) 20 to 30(When compressor is off: 20 to 40)
温度控制精度 Temperature control accuracy(g) 【1.0
湿度控制范围 Humidity setting range -
湿度控制精度 Humidity setting accuracy -
制冷功率 Cooling capacity(W) 550/650
加湿能力 Humidification capacity 2.6
允许环境温度 Allowable ambient temperature(篊) 20 to 35
允许环境湿度 Allowable ambient humidity(RH%) 10 to 85(No condensation)
外观 Appearance 重量 Weight(kg) Approx. 80
体积 Outside dimensions(mm) H965×W400×D615(Except flange)
Blower duct joint diameter(mm) ┆75
Coating color Unit: Ivory(JPMA: Y22-85B semi-gloss)
Controller: Dark gray(JPMA: Y55-40B semi-gloss)
电源 Electrical
characteristics
电源 Power supply 3 phase AC200V 50/60Hz
电流 Operating current 9.6/9.8
电机功率 Power consumption 3.2/33
组成装置 Components 压缩机 Compressor Rolling piston rotating type
Coolant, Coolant volume(g) HFC-134a 120
Condenser, Cooler Fin and tube
Heater Sheathed heater with fin(600W)
除湿器 Humidifier -
Blower air discharge rate 2.8/3.2
(*at connection duct 0.4/0.7 or higher)
8.0/9.4
Coolant controller Capillary tube
Temperature sensor IC Temperature sensor
Humidity sensor Polymer resistor
温度控制 Temperature controller Electronic digital setting indicating PID control
除湿控制 Humidity controller -

 

Note:
Temperature setting range:
These values are obtained at the air discharge port of the PAU unit in a surrounding environment of 25ìC/40% RH. The PAU unit may not offer the rated temperature control accuracy depending on the ambient temperature/humidity.

Blower air discharge rate:
Make sure that you do not excessively reduce the volume of the evolving airflow to prevent freezing. (For more information, please contact our sales representative.)

Cooling capacity:
These values are obtained in a surrounding environment of 25ìC/40% RH.

Allowable ambient temperature:
Performance does not cover all temperature control ranges.

Allowable ambient humidity:
Performance does not cover all humidity control ranges.

Humidifier:
Do not use ultra-pure water.

*The protection circuit for operation in low temperature operates in ambient temperatures of 18ìC or lower. (The unit recovers to its normal state at 20ìC or higher.)

*The humidity varies within a range of 【5% when the automatic blowing device is activated.

*The humidifier startup time differs depending on the temperature of the feed water for the humidifier.

[打印]  [关闭窗口]  

Warning: Unknown: Your script possibly relies on a session side-effect which existed until PHP 4.2.3. Please be advised that the session extension does not consider global variables as a source of data, unless register_globals is enabled. You can disable this functionality and this warning by setting session.bug_compat_42 or session.bug_compat_warn to off, respectively in Unknown on line 0