产品规格型号 Specification |
产品规格型号 Model | PAU unit | |
安装方式 Type | PAU-1400HDR | |
性能 Performance | 温度控制范围 Temperature setting range | 20 to 30(When compressor is off: 20 to 40) |
温度控制精度 Temperature control accuracy(g) | 【0.5 | |
湿度控制范围 Humidity setting range | - | |
湿度控制精度 Humidity setting accuracy | - | |
制冷功率 Cooling capacity(W) | 0.75kW : 2360/2800 0.4kW : 1060/1220 | |
加湿能力 Humidification capacity | - | |
允许环境温度 Allowable ambient temperature | (1), (3)20 to 30 / (2)25 to 30 | |
允许环境湿度 Allowable ambient humidity(RH%) | (1), (3)40 to 60 / (2)60 to 90 | |
外观 Appearance | 重量 Weight(kg) | 240 |
体积 Outside dimensions(mm) | H1450×W1200×D650 | |
Blower duct joint diameter(mm) | ?5 | |
Coating color | Unit: Ivory(JPMA: Y22-85B semi-gloss) Controller: Dark gray(JPMA: Y55-40B semi-gloss) | |
电源 Electrical characteristics |
电源 Power supply | 3 phase 200V 50/60Hz |
电流 Operating current | 28.4 | |
电机功率 Power consumption | 9.8 | |
组成装置Components | 压缩机 Compressor | 0.75kW/0.4kW |
Coolant, Coolant volume(g) | R-134a 120 | |
Condenser, Cooler | Fin and tube | |
Heater | Sheathed heater with fin(600W) | |
除湿器 Humidifier | 2kW | |
Blower air discharge rate | For control air 4m3 | |
For condenser Approx. 13.6/16.1 | ||
Coolant controller | Temperature expansion valve, Evaporating pressure control valve | |
Temperature sensor | Platinum resistance temperature sensor | |
Humidity sensor | Electronic digital setting indicating PID control | |
温度控制 Temperature controller | Electronic digital setting indicating PID control | |
除湿控制 Humidity controller | - |
Note:
Temperature setting range:
These values are obtained at the air discharge port of the PAU unit in a surrounding environment of 25ìC/40% RH. The PAU unit may not offer the rated temperature control accuracy depending on the ambient temperature/humidity.
Blower air discharge rate:
Make sure that you do not excessively reduce the volume of the evolving airflow to prevent freezing. (For more information, please contact our sales representative.)
Cooling capacity:
These values are obtained in a surrounding environment of 25ìC/40% RH.
Allowable ambient temperature:
Performance does not cover all temperature control ranges.
Allowable ambient humidity:
Performance does not cover all humidity control ranges.
Humidifier:
Do not use ultra-pure water.
*The protection circuit for operation in low temperature operates in ambient temperatures of 20ìC or lower. (The unit recovers to its normal state at 22ìC or higher.).
*The humidity varies within a range of 【5% when the automatic blowing device is activated.
*The humidifier startup time differs depending on the temperature of the feed water for the humidifier.