产品规格型号 Specification |
产品规格型号 Model | PAU unit | |
安装方式 Type | PAU-1300S-CU | |
性能 Performance | 温度控制范围 Temperature setting range | 20 to 30(When compressor is off: 20 to 40) |
温度控制精度 Temperature control accuracy(g) | 【0.5 | |
湿度控制范围 Humidity setting range | - | |
湿度控制精度 Humidity setting accuracy | - | |
制冷功率 Cooling capacity(W) | 1200/1400 (At ambient temperature of 25ìCì) | |
加湿能力 Humidification capacity | - | |
允许环境温度 Allowable ambient temperature | 20 to 35 | |
允许环境湿度 Allowable ambient humidity(RH%) | 10 to 85(No condensation) | |
外观 Appearance | 重量 Weight(kg) | 80 |
体积 Outside dimensions(mm) | H1065】W400】D700 (Except flange) | |
Blower duct joint diameter(mm) | ┆100 | |
Coating color | Unit: Ivory(JPMA: Y22-85B semi-gloss) Controller: Dark gray(JPMA: Y55-40B semi-gloss) | |
电源 Electrical characteristics |
电源 Power supply | 3phase AC200V 50/60Hz |
电流 Operating current | 11.5/13.2/2.1(50Hz) 11.8/12.9/1.9(60Hz) (At ambient temperature of 25ìCì) | |
电机功率 Power consumption | 2310/2340 (At ambient temperature of 25ìCì) | |
组成装置 Components | 压缩机 Compressor | Rolling piston rotating type |
Coolant, Coolant volume(g) | HFC-134a (240g) | |
Condenser, Cooler | Fin and tube | |
Heater | Sheathed heater with fin (2.0kw) | |
除湿器 Humidifier | - | |
Blower air discharge rate | 4.4/4.9 (3.3/4.0) | |
5.0/6.0】2 | ||
Coolant controller | Capillary tube | |
Temperature sensor | Thermocouple(Type K) | |
Humidity sensor | - | |
温度控制 Temperature controller | Electronic digital setting indicating PID control | |
除湿控制 Humidity controller | - |
Note:
Temperature setting range:
These values are obtained at the air discharge port of the PAU unit in a surrounding environment of 25ìC/40% RH. The PAU unit may not offer the rated temperature control accuracy depending on the ambient temperature/humidity.
Blower air discharge rate:
Make sure that you do not excessively reduce the volume of the evolving airflow to prevent freezing. (For more information, please contact our sales representative.)
Cooling capacity:
These values are obtained in a surrounding environment of 25ìC/40% RH.
Allowable ambient temperature:
Performance does not cover all temperature control ranges.
*The protection circuit for operation in low temperature operates in ambient temperatures of 18ìC or lower. (The unit recovers to its normal state at 20ìC or higher.).