您现在的位置  首页 >> 代理贸易业务 >> Apiste PAU精密空调 >> PAU精密空调 >> [ PAU-AR800S ]

产品名称:PAU-AR800S
产品型号:PAU-AR800S
上传时间:2012-06-01
点击次数:11365

   

产品规格型号  Specification
产品规格型号 Model PAU unit
安装方式 Type PAU-AR800S
性能 Performance 温度控制范围 Temperature control range(ºC) 20 to 30
温度控制精度 Temperature control accuracy(ºC) ±0.1
制冷功率 Cooling capacity(W) 550/650 (At outlet port of the main unit)
450/550 (At the end of a 4m duct connected with one 90º bend)
允许环境温度 Allowable ambient temperature(ºC) 20 to 35
允许环境湿度 Allowable ambient humidity(RH%) 10 to 85 (No condensation)
外观 Appearance 体积 Outside dimensions(mm) H865×W400×D400 (except flange)
重量 Weight(kg) 52
Blower duct joint diameter(mm) ø75
Coating color Unit Ivory (JPMA: Y22-85B semi-gloss)
Controller Dark gray (JPMA: Y55-40B semi-gloss)
电源 Electrical
characteristics
电源 Power supply  1phase AC100V 50/60Hz 
电流 Operating current(MIN)
             (MAX)  (A)
14.1/14.6
Power consumption(MIN)
Operating current(MAX)  (W)
1370/1460
组成装置Components Compressor, Coolant Rolling piston rotating type, HFC-134a
Condenser, Cooler Fin and tube
Heater Sheathed heater with fin (1kW)
Coolant controller Capillary tube
Temperature sensor IC Temperature sensor
温度控制 Temperature control Electronic digital setting indicating PID control
保护装置Protective
device
Main circuit Ground leakage breaker (15A 15mA)
Blower fan(For cooler) Delay timer (For 3 minutes)
压缩机 Compressor Low temperature overheat protection thermostat (18ºC OFF   20ºC ON)
Overcurrent relay (Manual reset) (9.0A)
Motor protector (100ºC OFF   80ºC ON)
Surge-absorbing unit
Heater Overheat protection thermostat (65ºC OFF   55ºC ON)
Thermal fuse (99ºC OFF)
Surge-absorbing unit
Alarm
device
Alarm lamp Lamp illuminates

Note:
Temperature setting range:
These values are obtained at the air discharge port of the PAU unit in a surrounding environment of 25/40% RH. The PAU unit may not offer the rated temperature control accuracy depending on the ambient temperature/humidity.

Blower air discharge rate:
Make sure that you do not excessively reduce the volume of the evolving airflow to prevent freezing. (For more information, please contact our sales representative.)

Cooling capacity:
These values are obtained in a surrounding environment of 25/40% RH.

Allowable ambient temperature:
Performance does not cover all temperature control ranges.
[打印]  [关闭窗口]  

Warning: Unknown: Your script possibly relies on a session side-effect which existed until PHP 4.2.3. Please be advised that the session extension does not consider global variables as a source of data, unless register_globals is enabled. You can disable this functionality and this warning by setting session.bug_compat_42 or session.bug_compat_warn to off, respectively in Unknown on line 0