您现在的位置  首页 >> 代理贸易业务 >> Apiste ENC电气柜空调 >> ENC电气柜空调 >> [ ENC-G310EX/G320EX ]

产品名称:ENC-G310EX/G320EX
产品型号:ENC-G310EX/G320EX
上传时间:2015-02-04
点击次数:9902

   

 产品规格型号(Specification

产品规格型号[Model]

ENC-G310EX ENC-G320EX
安装方式[Type] Top mount type(置顶式)
制冷方式[Cooling scheme] Compressor(压缩机制冷)
制冷功率[Cooling capacity](W) 280/300 (50/60Hz)

电源[Power supply] (50/60Hz)

1 phase 100VAC±0% 1 phase 200VAC±10%
电流[Current consumption] (A)(MAX) 4.0/4.2 1.9/1.7
启动电流[Starting current] (A) 7.4/7.7 4.0/4.2
电机功率[Power consumption] (W)(MAX) 360/410 340/330
允许环境温度[Allowable ambient temperature] (℃) 20 to 50
允许环境湿度[Allowable ambient humidity] (%) 10 to 85 (No condensation)
制冷剂[Refrigerant] R-134a 90g (A kind of freon that is not prohibited)
温度[Temperature control range](℃) 25 to 45
风机[Number of fans] 2
输出[Output] Output of operation & alarm(250V 2A)
显示[Display]
LED Temperature/Error RUN
抗噪音水平[Noise immunity]
Level 4 in the fast transient/Burst immunity test
噪音值[Noise] (dB) Approx. 62/65
振动[Vibration resistance] Vibration frequency : 5Hz ; a double amplitude of 20mm
颜色[Paint color] Munsell 5Y7/1 Equivalent color of light beige
体积[Outer dimensions] (mm) H230×W590×D200
重量[Weight](kg) 16

Note:
Cooling capacity:
Rated value at an ambient temperature of 35°and an internal temperature of 35° (Measured according to the enthalpy method in JIS-C-9612)
Rated value:
Measured under an ambient temperature of 35° and a relative humidity of 40%
Maximum value:
Measured under the highest allowable temperature ambient temperature and a relative humidity of 40%
Allowable ambient temperature:
When you use an FA cooler continuously at an ambient temperature below 15-20° in low temperature periods, turn off the power supply whenever possible, because there is possibility of compressor being operated under high load.
[打印]  [关闭窗口]  

Warning: Unknown: Your script possibly relies on a session side-effect which existed until PHP 4.2.3. Please be advised that the session extension does not consider global variables as a source of data, unless register_globals is enabled. You can disable this functionality and this warning by setting session.bug_compat_42 or session.bug_compat_warn to off, respectively in Unknown on line 0