您现在的位置  首页 >> 代理贸易业务 >> Apiste PAU精密空调 >> PAU精密空调 >> [ PAU-1400HDR ]

产品名称:PAU-1400HDR
产品型号:PAU-1400HDR
上传时间:2012-06-01
点击次数:8219

   

产品规格型号  Specification
产品规格型号 Model PAU unit
安装方式 Type PAU-1400HDR
性能 Performance 温度控制范围 Temperature setting range 20 to 30(When compressor is off: 20 to 40)
温度控制精度 Temperature control accuracy(g) 【0.5
湿度控制范围 Humidity setting range -
湿度控制精度 Humidity setting accuracy -
制冷功率 Cooling capacity(W) 0.75kW : 2360/2800 0.4kW : 1060/1220
加湿能力 Humidification capacity -
允许环境温度 Allowable ambient temperature (1), (3)20 to 30 / (2)25 to 30
允许环境湿度 Allowable ambient humidity(RH%) (1), (3)40 to 60 / (2)60 to 90
外观 Appearance 重量 Weight(kg) 240
体积 Outside dimensions(mm) H1450×W1200×D650
Blower duct joint diameter(mm) ?5
Coating color Unit: Ivory(JPMA: Y22-85B semi-gloss)
Controller: Dark gray(JPMA: Y55-40B semi-gloss)
电源 Electrical
characteristics
电源 Power supply 3 phase 200V 50/60Hz
电流 Operating current 28.4
电机功率 Power consumption 9.8
组成装置Components 压缩机 Compressor 0.75kW/0.4kW
Coolant, Coolant volume(g) R-134a 120
Condenser, Cooler Fin and tube
Heater Sheathed heater with fin(600W)
除湿器 Humidifier 2kW
Blower air discharge rate For control air 4m3
For condenser Approx. 13.6/16.1
Coolant controller Temperature expansion valve, Evaporating pressure control valve
Temperature sensor Platinum resistance temperature sensor
Humidity sensor Electronic digital setting indicating PID control
温度控制 Temperature controller Electronic digital setting indicating PID control
除湿控制 Humidity controller -

 

Note:
Temperature setting range:
These values are obtained at the air discharge port of the PAU unit in a surrounding environment of 25ìC/40% RH. The PAU unit may not offer the rated temperature control accuracy depending on the ambient temperature/humidity.

Blower air discharge rate:
Make sure that you do not excessively reduce the volume of the evolving airflow to prevent freezing. (For more information, please contact our sales representative.)

Cooling capacity:
These values are obtained in a surrounding environment of 25ìC/40% RH.

Allowable ambient temperature:
Performance does not cover all temperature control ranges.

Allowable ambient humidity:
Performance does not cover all humidity control ranges.

Humidifier:
Do not use ultra-pure water.

*The protection circuit for operation in low temperature operates in ambient temperatures of 20ìC or lower. (The unit recovers to its normal state at 22ìC or higher.).

*The humidity varies within a range of 【5% when the automatic blowing device is activated.

*The humidifier startup time differs depending on the temperature of the feed water for the humidifier.

[打印]  [关闭窗口]  

Warning: Unknown: Your script possibly relies on a session side-effect which existed until PHP 4.2.3. Please be advised that the session extension does not consider global variables as a source of data, unless register_globals is enabled. You can disable this functionality and this warning by setting session.bug_compat_42 or session.bug_compat_warn to off, respectively in Unknown on line 0